Accordingly, the NOJA Power Test Laboratory is now certified to provide type testing services on electrical switchgear and mechanical assemblies, such as:
The NOJA Power Test Laboratory team celebrating their accreditation to IEC/ISO17025, joined by NOJA Power Group Managing Director Neil O’Sulliivan (Left) and Group Quality and Service Director Oleg Samarski (2nd from left).
The accredited laboratory is situated in Brisbane, Australia, at NOJA Power’s corporate headquarters and manufacturing campus.
“NOJA Power has operated our high voltage laboratory now for 11 years for our own internal R&D purposes,” says NOJA Power Group Managing Director Neil O’Sullivan.“ Supported by 3rd party calibration services our independent experienced laboratory team are now capable of not only certifying our future product developments but also offering independent testing and calibration services to our customers and electrical equipment manufacturers.”
“This is a great credit to the NOJA Power Test Laboratory and shows the high standard of work produced,” reports NOJA Power Test Laboratory Manager Sam Griffiths.“ This will also open up a variety of different possibilities for the test laboratory.”
The NOJA Power Test Laboratory full accreditation list is available here and summarised in table 1. With the laboratory accreditation secured, NOJA Power is accepting laboratory bookings from Q1 2021. To enquire regarding laboratory availability and scheduling, contact NOJA Power at www.nojapower.com.au.
Table 1 – NOJA Power’s ISO 17025:2017 Accredited Test Capabilities
Type Test Technology | Test Methods | |
---|---|---|
Dielectric | Power Frequency voltage Up to 150 kV, 1.5 A, 50/60 Hz Lightning Impulse voltage 600 kV, 60 kJ |
IEC 60060-1, IEC 62271-1, IEC 62271-100, -103, -111, IEC 60137, IEC 61869-1, -3 IEC 60060-1, IEC 62271-1 IEC 62271-100, -103, -111, IEC 61869-1, IEC 60137 |
Partial discharge 5 – 100 pC |
IEC 60270, IEC 62271-1, IEC 62271-111, IEC 60137, IEC 61869-1 | |
Environmental Chamber | Cold, Dry and Damp Heat Cycle Temperature: -65 °C to + 110 °C Climate Chamber: 1 m x 1 m x 1 m |
IEC 60068-2-1, IEC 60068-2-2,IEC 60068-2-30 |
Mechanical Operation | IEC 62271-1, IEC 62271-100, -103, -111 | |
Temperature Rise | Single-phase/three-phase up to 3000 A 50/60 Hz | IEC 62271-1, IEC 61869-1, -3, IEC 62271-100, -103, -111, IEC 60137 |
Salt Fog | 1000 Hour Test Voltage: 2 kV to 30 kV Chamber Size: 1100 mm x 600 mm x 1300 mm | IEC 62217 |
Contact Resistance Measurement | 100–1000μΩ at 1A, 50–500μΩ at 10A, 50–500μΩ at 100A |